upsRebootWithDuration

ups Reboot With Duration
1.3.6.1.2.1.33.1.8.4

Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.

Back to rfc1628 MIB page.

IPHost Network monitor uses SNMP for monitoring health and availability of devices and applications in your network. You can send a SNMP Set to any remote device to monitor a specific SNMP object (CPU, Memory, Disk, Server Temperature, RAID failures, IO statistics, connection counts, error and much more).