xupsLoadShedSecsWithRestart

xups Load Shed Secs With Restart

Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsControlOutputOffDelay, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted. This is the preferred Control object to use when performing an On Battery OS Shutdown.

Back to XUPS-MIB MIB page.

IPHost Network monitor allows you to monitor xupsLoadShedSecsWithRestart on Eaton device via the SNMP protocol. Download IPHost Network Monitor (500 monitors for 30 days, 50 monitors free forever) to start monitoring Eaton UPSes right now.