upsAdvConfigHighTransferVolt - ups Adv Config High Transfer Volt - PowerNet-MIB

MIBs list

With IPHost Network Monitor you can run simple snmp requests against a Dell device in your network.

upsAdvConfigHighTransferVolt

ups Adv Config High Transfer Volt
1.3.6.1.4.1.318.1.1.1.5.2.2

The maximum line voltage in VAC allowed before the UPS system transfers to battery backup. Allowed values depend on the UPS used: 100 volt units allow settings of 108, 110, 112, and 114. 120 volt units allow settings of 129, 132, 135, and 138. 208 volt units allow settings of 224, 229, 234, and 239. 230 volt units allow settings of 253, 264, 271, and 280. Matrix Notes: Matrix units configured for 208V input allow settings of 240, 244, 248, and 252. Matrix units configured for 240V input allow settings of 276, 264, 253, and 282. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.

Back to PowerNet-MIB MIB page.

IPHost Network monitor allows you to monitor upsAdvConfigHighTransferVolt on Dell device via the SNMP protocol. Download IPHost Network Monitor (500 monitors for 30 days, 50 monitors free forever) to start monitoring Dell switches right now.