MG-SNMP-UPS-MIB DEFINITIONS ::= BEGIN -- Title: UPS MIB -- Date: October 11, 1995 -- Author: MGE UPS SYSTEMS -- Release: V1.6 -- Date: October 23, 2003 -- Author: MGE UPS SYSTEMS -- Release: V1.7 AB - Add variables for Environment sensor, see comments beginning with AB Release -- Date: November 22, 2004 -- Author: MGE UPS SYSTEMS - PV -- Release: V1.7 AC - Add compatibility with SMI V2 -- Date: December 19, 2006 -- Author: MGE UPS SYSTEMS -- Release: V1.7 AD - Add traps 65 and 66 about Redundancy IMPORTS enterprises,IpAddress,TimeTicks FROM RFC1155-SMI DisplayString FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215; ---- -- Path to the root ---- merlinGerin OBJECT IDENTIFIER ::= { enterprises 705 } upsmg OBJECT IDENTIFIER ::= { merlinGerin 1 } -- Management and Configuration groups of the MIB upsmgIdent OBJECT IDENTIFIER ::= { upsmg 1 } upsmgManagement OBJECT IDENTIFIER ::= { upsmg 2 } upsmgReceptacle OBJECT IDENTIFIER ::= { upsmg 3 } upsmgConfig OBJECT IDENTIFIER ::= { upsmg 4 } -- UPS Monitoring groups of the MIB upsmgBattery OBJECT IDENTIFIER ::= { upsmg 5 } upsmgInput OBJECT IDENTIFIER ::= { upsmg 6 } upsmgOutput OBJECT IDENTIFIER ::= { upsmg 7 } upsmgEnviron OBJECT IDENTIFIER ::= { upsmg 8 } -- UPS Controlling groups of the MIB upsmgControl OBJECT IDENTIFIER ::= { upsmg 9 } upsmgTest OBJECT IDENTIFIER ::= { upsmg 10 } upsmgTraps OBJECT IDENTIFIER ::= { upsmg 11 } upsmgAgent OBJECT IDENTIFIER ::= { upsmg 12 } upsmgRemote OBJECT IDENTIFIER ::= { upsmg 13 } ---- -- Definition of object types ---- -- Management and Configuration groups of the MIB: -- upsmgIdent(1), upsmgManagement(2), upsmgReceptacle(3), upsmgConfig(4) -------------------------- -- the upsmgIdent group -- -------------------------- upsmgIdentFamilyName OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "The UPS family name (e.g. `PULSAR', `COMET', `GALAXY', ...)." ::= { upsmgIdent 1 } upsmgIdentModelName OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "The UPS model name (e.g. `PSX20', `SV9', ... )." ::= { upsmgIdent 2 } upsmgIdentRevisionLevel OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "The UPS revision level." ::= { upsmgIdent 3 } upsmgIdentFirmwareVersion OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "The UPS microprocessor firmware version number." ::= { upsmgIdent 4 } upsmgIdentUserID OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "The UPS user identification (set by administrator)." ::= { upsmgIdent 5 } upsmgIdentInstallationDate OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "The UPS installation date in dd/mm/yy format." ::= { upsmgIdent 6 } upsmgIdentSerialNumber OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "The UPS manufacturing serial number." ::= { upsmgIdent 7 } -------------------------- -- the upsmgManagement group -- -------------------------- -- This group gives objects for description of a list of Managers. -- A management platform is identified, can be powered by the UPS, -- and is allowed to a certain level of management. upsmgManagersNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of managers that could manage the UPS." ::= { upsmgManagement 1 } upsmgManagersTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgManagersEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of managers." ::= { upsmgManagement 2 } upsmgManagersEntry OBJECT-TYPE SYNTAX UpsmgManagersEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of a manager entry in the managers table." INDEX { mgmanagerIndex } ::= { upsmgManagersTable 1 } UpsmgManagersEntry ::= SEQUENCE { -- ASN.1 type definition mgmanagerIndex INTEGER, mgmanagerDeviceNumber INTEGER, mgmanagerNMSType INTEGER, mgmanagerCommType INTEGER, mgmanagerDescr DisplayString, mgmanagerAddress IpAddress, mgmanagerCommunity DisplayString, mgmanagerSeverityLevel INTEGER, mgmanagerTrapAck INTEGER } mgmanagerIndex OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "A unique value for each manager. Its value ranges between 1 and the value of upsmgManagersNum." ::= { upsmgManagersEntry 1 } mgmanagerDeviceNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "This object is the number of the manager device in the DevicesTable of the Config group. This means that the manager is powered by the UPS. If not the default value is 0." ::= { upsmgManagersEntry 2 } mgmanagerNMSType OBJECT-TYPE SYNTAX INTEGER { umclient(1), decnetview(2), umview(3), dview(4), hpopenview(5), sunnetmanager(6), novellnms(7), ibmnetview(8), other(9), autolearning(10) } ACCESS read-write STATUS mandatory DESCRIPTION "The type of manager according to the NMS platform. We include in the manager class all systems which will be notified by the agent via receiving traps (e.g. basic to complex NMS software)." ::= { upsmgManagersEntry 3 } mgmanagerCommType OBJECT-TYPE SYNTAX INTEGER { other(1), -- none of the following invalid(2), -- an invalidated manager cmip(3), -- OSI CMIP snmpv1(4), -- SNMPv1 snmpv2(5) -- SNMPv2 } ACCESS read-write STATUS mandatory DESCRIPTION "The level of communication protocol for that manager. Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgManagersTable. It is an implementation-specific matter as to wether the agent removes an invalidated entry from the table. Accordingly, management stations must be prepared to receive tabular information from agents that corresponds to entry not currently in use. Proper interpretation of such entries requires examination of the relevant mgmanagerCommType object." ::= { upsmgManagersEntry 4 } mgmanagerDescr OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "A textual string containing information about the manager. (manufacturer and version description)." ::= { upsmgManagersEntry 5 } mgmanagerAddress OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The IP address of the manager station receiving traps. The value of this object is meaningful if and only if the value of the relevant mgmanagerCommType object is snmp type." ::= { upsmgManagersEntry 6 } mgmanagerCommunity OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "The manager community string." ::= { upsmgManagersEntry 7 } mgmanagerSeverityLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The severity level of traps to be received by this manager." ::= { upsmgManagersEntry 8 } mgmanagerTrapAck OBJECT-TYPE SYNTAX INTEGER { mgack(1), mgnoack(2), stdnomg(3), mgacks(4), cpqnoack(5) } ACCESS read-write STATUS mandatory DESCRIPTION "The manager Trap Acknowledgement status. Setting this object to mgnoack(2) or stdnomg(3) or cpqnoack(5) disables the trap acknowledgement from the related manager. The MG enterprise specific trap should then be sent only once by the agent to this manager in case of mgnoack(2), and should not be sent by the agent to this manager in case of stdnomg(3) or cpqnoack(5). mgack(1) allows a basic mecanism for acknowledged traps using upsmgAgentTrapAck object set by the manager to the enterprise specific number of the trap. mgacks(5) allows the enhanced mecanism using the upsmgAgentTrapSignature object set by the manager to the signature received within the trap var binding." ::= { upsmgManagersEntry 9 } -------------------------- -- the upsmgReceptacle group -- -------------------------- -- This group gives objects for description of the receptacles of the -- UPS. The receptacle notion has been extended to many configurations: -- For a small simple UPS, there is only one receptacle which corresponds -- to the output of the UPS. -- For a more complex UPS with powershare capabilities, there is a one-level -- receptacle table allowing to distribute ON/OFF control on the receptacles. -- For others (EHQ, big UPS with Distributed Power Units), there is a -- two-level receptacle table allowing to distribute control and management -- of the receptacles plugs into one of the first level receptacles. upsmgReceptaclesNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The total number of receptacles controlled by the UPS." ::= { upsmgReceptacle 1 } upsmgReceptaclesTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgReceptaclesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of receptacles that are controlled by the UPS." ::= { upsmgReceptacle 2 } upsmgReceptaclesEntry OBJECT-TYPE SYNTAX UpsmgReceptaclesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of a receptacle in the table." INDEX { mgreceptacleIndex } ::= { upsmgReceptaclesTable 1 } UpsmgReceptaclesEntry ::= SEQUENCE { -- ASN.1 type definition mgreceptacleIndex INTEGER, mgreceptacleLevel INTEGER, mgreceptacleType DisplayString, mgreceptacleIdent DisplayString, mgreceptacleState INTEGER, mgreceptacleReceptacle INTEGER, mgreceptaclePowerCons INTEGER, mgreceptacleOverload INTEGER, mgreceptacleAutonomy INTEGER } mgreceptacleIndex OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "A unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum." ::= { upsmgReceptaclesEntry 1 } mgreceptacleLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The level of receptacle. Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgReceptaclesTable. It is an implementation-specific matter as to wether the agent removes an invalidated entry from the table. Accordingly, management stations must be prepared to receive tabular information from agents that corresponds to entry not currently in use. Proper interpretation of such entries requires examination of the relevant receptacleLevel object. Values 1 and 4 are reserved, value 3 is used to identify a simple one-level receptacle, and values greater than 4 represent a group of equivalent receptacles." ::= { upsmgReceptaclesEntry 2 } mgreceptacleType OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "A textual string for the receptacle type." ::= { upsmgReceptaclesEntry 3 } mgreceptacleIdent OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "A textual string identification for the user." ::= { upsmgReceptaclesEntry 4 } mgreceptacleState OBJECT-TYPE SYNTAX INTEGER { manualON(1), -- after manual turn on manualOFF(2), -- after manual turn off normalON(3), -- after normal restart sequence normalOFF(4), -- after normal shutoff sequence controlON(5), -- after upsControl on command controlOFF(6), -- after upsControl off command scheduleON(7), -- after schedule turn on scheduleOFF(8) -- after schedule turn off } ACCESS read-only STATUS mandatory DESCRIPTION "The ON/OFF status of the receptacle." ::= { upsmgReceptaclesEntry 5 } mgreceptacleReceptacle OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The receptacle number of the second level receptacle father. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is 0." ::= { upsmgReceptaclesEntry 6 } mgreceptaclePowerCons OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The volt-ampere rating of the receptacle. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is 0." ::= { upsmgReceptaclesEntry 7 } mgreceptacleOverload OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The overload status of the receptacle. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is 0." ::= { upsmgReceptaclesEntry 8 } mgreceptacleAutonomy OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The receptacle autonomy. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is 0." ::= { upsmgReceptaclesEntry 9 } -------------------------- -- the upsmgConfig group -- -------------------------- -- This group gives objects for describing: -- Battery characteristics and administrative status, -- Configuration set points for normal shutoff and restart, -- Nominal voltage and Input low/high transfer point, -- Output and By Pass characteristics, -- Devices table (powered systems), -- Receptacles default table. -- Environ external alarms UserID table. -- Battery characteristics and administrative status. upsmgConfigBatteryInstalled OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The battery installed status." ::= { upsmgConfig 1 } upsmgConfigNominalBatteryVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The nominal battery voltage." ::= { upsmgConfig 2 } upsmgConfigNominalBatteryTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The full load battery autonomy time." ::= { upsmgConfig 3 } upsmgConfigNominalRechargeTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The recharge time to go from low battery cut off to full charge at full load." ::= { upsmgConfig 4 } -- Configuration set points for normal shutoff and restart. upsmgConfigMinRechargeLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The minimum battery level required to supply power on the loads after low battery condition turn off and restart on main return." ::= { upsmgConfig 5 } upsmgConfigMaxRechargeTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The maximum time delay of battery recharge before supply power to the loads." ::= { upsmgConfig 6 } upsmgConfigLowBatteryTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set remaining time value for low battery condition." ::= { upsmgConfig 7 } upsmgConfigLowBatteryLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set battery level value for low battery condition." ::= { upsmgConfig 8 } upsmgConfigAutoRestart OBJECT-TYPE SYNTAX INTEGER { always(1), never(2), onmain(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The automatic restart enabling status." ::= { upsmgConfig 9 } upsmgConfigShutdownTimer OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set ups shutdown timer from on battery condition." ::= { upsmgConfig 10 } upsmgConfigSysShutDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set ups shutdown delay (Sn delay)." ::= { upsmgConfig 11 } -- Nominal voltage and Input low/high transfer point. upsmgConfigVARating OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The UPS nominal VA rating." ::= { upsmgConfig 12 } upsmgConfigLowTransfer OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The low voltage transfer point." ::= { upsmgConfig 13 } upsmgConfigHighTransfer OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The high voltage transfer point." ::= { upsmgConfig 14 } -- Output and By Pass characteristics. upsmgConfigOutputNominalVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The nominal output voltage." ::= { upsmgConfig 15 } upsmgConfigOutputNominalCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The nominal output current." ::= { upsmgConfig 16 } upsmgConfigOutputNomFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The nominal output frequency." ::= { upsmgConfig 17 } upsmgConfigByPassType OBJECT-TYPE SYNTAX INTEGER { none(1), relay(2), static(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The UPS by pass switch type." ::= { upsmgConfig 18 } upsmgConfigAlarmAudible OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "To set audible alarm status." ::= { upsmgConfig 19 } upsmgConfigAlarmTimeDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set audible alarm time delay." ::= { upsmgConfig 20 } -- Devices table (powered systems). upsmgConfigDevicesNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The number of devices that are powered by the UPS." ::= { upsmgConfig 21 } upsmgConfigDevicesTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgConfigDevicesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of devices that are powered by the UPS." ::= { upsmgConfig 22 } upsmgConfigDevicesEntry OBJECT-TYPE SYNTAX UpsmgConfigDevicesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of a device entry in the devices table." INDEX { mgdeviceIndex } ::= { upsmgConfigDevicesTable 1 } UpsmgConfigDevicesEntry ::= SEQUENCE { -- ASN.1 type definition mgdeviceIndex INTEGER, mgdeviceReceptacleNum INTEGER, mgdeviceIdent DisplayString, mgdeviceVaRating INTEGER, mgdeviceSequenceOff INTEGER, mgdeviceSequenceOn INTEGER, mgdeviceShutdownDuration INTEGER, mgdeviceBootUpDuration INTEGER } mgdeviceIndex OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "A unique value for each device. Its value ranges between 1 and the value of upsmgDevicesNum." ::= { upsmgConfigDevicesEntry 1 } mgdeviceReceptacleNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The receptacle number of the device plugged into the UPS. This value gives index entry in the ReceptaclesTable object of the Receptacle group. A value of 0 invalidates the entry in the DevicesTable." ::= { upsmgConfigDevicesEntry 2 } mgdeviceIdent OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "A textual string for device user identification." ::= { upsmgConfigDevicesEntry 3 } mgdeviceVaRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The volt-ampere rating of the device plugged into the UPS." ::= { upsmgConfigDevicesEntry 4 } mgdeviceSequenceOff OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set the device position in the remote shutdown sequence." ::= { upsmgConfigDevicesEntry 5 } mgdeviceSequenceOn OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set the device position in the remote reboot sequence." ::= { upsmgConfigDevicesEntry 6 } mgdeviceShutdownDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set the duration from start of computer shut-down to complete." ::= { upsmgConfigDevicesEntry 7 } mgdeviceBootUpDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set the duration from start of computer boot-up to complete." ::= { upsmgConfigDevicesEntry 8 } -- Receptacles default table. -- This table gives for every receptacle the power return condition for -- each failure cause. upsmgConfigReceptaclesTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgConfigReceptaclesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of receptacles." ::= { upsmgConfig 23 } upsmgConfigReceptaclesEntry OBJECT-TYPE SYNTAX UpsmgConfigReceptaclesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of a receptacle entry in the table." INDEX { mgreceptacleIndexb } ::= { upsmgConfigReceptaclesTable 1 } UpsmgConfigReceptaclesEntry ::= SEQUENCE { -- ASN.1 type definition mgreceptacleIndexb INTEGER, mgreceptacleStateTurnOn INTEGER, mgreceptacleStateMainReturn INTEGER, mgreceptacleStateDischarge INTEGER, mgreceptacleShutoffLevel INTEGER, mgreceptacleShutoffTimer INTEGER, mgreceptacleRestartLevel INTEGER, mgreceptacleRestartDelay INTEGER, mgreceptacleShutdownDuration INTEGER, mgreceptacleBootUpDuration INTEGER } mgreceptacleIndexb OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "A unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum." ::= { upsmgConfigReceptaclesEntry 1 } mgreceptacleStateTurnOn OBJECT-TYPE SYNTAX INTEGER { on(1), off(2), last(3), schedule(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Default return state at turn on." ::= { upsmgConfigReceptaclesEntry 2 } mgreceptacleStateMainReturn OBJECT-TYPE SYNTAX INTEGER { on(1), off(2), last(3), schedule(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Default return state on main return." ::= { upsmgConfigReceptaclesEntry 3 } mgreceptacleStateDischarge OBJECT-TYPE SYNTAX INTEGER { on(1), off(2), last(3), schedule(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Default return state on main return from battery discharge." ::= { upsmgConfigReceptaclesEntry 4 } mgreceptacleShutoffLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery level for starting shutoff sequence." ::= { upsmgConfigReceptaclesEntry 5 } mgreceptacleShutoffTimer OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Time delay from on battery for starting shutoff sequence." ::= { upsmgConfigReceptaclesEntry 6 } mgreceptacleRestartLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Battery level for starting restart sequence." ::= { upsmgConfigReceptaclesEntry 7 } mgreceptacleRestartDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Time delay for starting restart sequence." ::= { upsmgConfigReceptaclesEntry 8 } mgreceptacleShutdownDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Maximum Shutdown Duration for systems powered by this plug." ::= { upsmgConfigReceptaclesEntry 9 } mgreceptacleBootUpDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Maximum Reboot Duration for systems powered by this plug." ::= { upsmgConfigReceptaclesEntry 10 } -- Environ external alarms UserID table. upsmgConfigExtAlarmNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of environ external alarm, value is between 8 and 32.." ::= { upsmgConfig 24 } upsmgConfigExtAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgConfigExtAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of environmental external alarms." ::= { upsmgConfig 25 } upsmgConfigExtAlarmEntry OBJECT-TYPE SYNTAX UpsmgConfigExtAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of an external alarm in the table." INDEX { mgextAlarmIndex } ::= { upsmgConfigExtAlarmTable 1 } UpsmgConfigExtAlarmEntry ::= SEQUENCE { -- ASN.1 type definition mgextAlarmIndex INTEGER, mgextAlarmUID DisplayString } mgextAlarmIndex OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "A unique value for each external alarm. Its value ranges between 1 and the value of upsmgConfigExtAlarmNum." ::= { upsmgConfigExtAlarmEntry 1 } mgextAlarmUID OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "A textual string for alarm state user identification." ::= { upsmgConfigExtAlarmEntry 2 } upsmgConfigEmergencyTestFail OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The emergency condition status on Battery test fail." ::= { upsmgConfig 26 } upsmgConfigEmergencyOnByPass OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The emergency condition status on By Pass." ::= { upsmgConfig 27 } upsmgConfigEmergencyOverload OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The emergency condition status on overload." ::= { upsmgConfig 28 } -- Schedule on/off daily time table. upsmgConfigControlDayTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgConfigControlDayEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of daily on/off time." ::= { upsmgConfig 29 } upsmgConfigControlDayEntry OBJECT-TYPE SYNTAX UpsmgConfigControlDayEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of a daily on/off time schedule in the table." INDEX { mgcontrolDayIndex } ::= { upsmgConfigControlDayTable 1 } UpsmgConfigControlDayEntry ::= SEQUENCE { -- ASN.1 type definition mgcontrolDayIndex INTEGER, mgcontrolDayOn INTEGER, mgcontrolDayOff INTEGER } mgcontrolDayIndex OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "The day index. It is a number between 1 and 7, 1 for Sunday, 2 for Monday, ..." ::= { upsmgConfigControlDayEntry 1 } mgcontrolDayOn OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set daily power on time. Any value greater than 86400 is to disable the Day On." ::= { upsmgConfigControlDayEntry 2 } mgcontrolDayOff OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set daily power off time. Any value greater than 86400 is to disable the Day Off." ::= { upsmgConfigControlDayEntry 3 } upsmgConfigLowBooster OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set UPS booster low threshold." ::= { upsmgConfig 30 } upsmgConfigHighBooster OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set UPS booster high threshold." ::= { upsmgConfig 31 } upsmgConfigLowFader OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set UPS fader low threshold." ::= { upsmgConfig 32 } upsmgConfigHighFader OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To set UPS fader high threshold." ::= { upsmgConfig 33 } -- AB Release on 2003/10/23 : Add Configuration of the environment sensor. upsmgConfigEnvironmentTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgConfigEnvironmentEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table containing the configuration of the environment sensor." ::= { upsmgConfig 34 } upsmgConfigEnvironmentEntry OBJECT-TYPE SYNTAX UpsmgConfigEnvironmentEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of an entry in the table." INDEX { upsmgConfigSensorIndex } ::= { upsmgConfigEnvironmentTable 1 } UpsmgConfigEnvironmentEntry ::= SEQUENCE { -- ASN.1 type definition upsmgConfigSensorIndex INTEGER, upsmgConfigSensorName DisplayString, upsmgConfigTemperatureLow INTEGER, upsmgConfigTemperatureHigh INTEGER, upsmgConfigTemperatureHysteresis INTEGER, upsmgConfigHumidityLow INTEGER, upsmgConfigHumidityHigh INTEGER, upsmgConfigHumidityHysteresis INTEGER, upsmgConfigInput1Name DisplayString, upsmgConfigInput1ClosedLabel DisplayString, upsmgConfigInput1OpenLabel DisplayString, upsmgConfigInput2Name DisplayString, upsmgConfigInput2ClosedLabel DisplayString, upsmgConfigInput2OpenLabel DisplayString } upsmgConfigSensorIndex OBJECT-TYPE SYNTAX INTEGER (0..50) ACCESS read-only STATUS mandatory DESCRIPTION "The sensor index, ranging from 1 to upsmgEnvironmentNum." ::= { upsmgConfigEnvironmentEntry 1 } upsmgConfigSensorName OBJECT-TYPE SYNTAX DisplayString(SIZE(0..42)) ACCESS read-write STATUS mandatory DESCRIPTION "The sensor user-friendly name." ::= { upsmgConfigEnvironmentEntry 2 } upsmgConfigTemperatureLow OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The low temperature threshold in unit 0.1 Cel." ::= { upsmgConfigEnvironmentEntry 3 } upsmgConfigTemperatureHigh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The high temperature threshold in unit 0.1 Cel." ::= { upsmgConfigEnvironmentEntry 4 } upsmgConfigTemperatureHysteresis OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The temperature hysteresys used for threshold test in unit 0.1 Cel." ::= { upsmgConfigEnvironmentEntry 5 } upsmgConfigHumidityLow OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The low humidity threshold in unit 1 %." ::= { upsmgConfigEnvironmentEntry 6 } upsmgConfigHumidityHigh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The high humidity threshold in unit 1 %." ::= { upsmgConfigEnvironmentEntry 7 } upsmgConfigHumidityHysteresis OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The humidity hysteresys used for threshold test in unit 1 %." ::= { upsmgConfigEnvironmentEntry 8 } upsmgConfigInput1Name OBJECT-TYPE SYNTAX DisplayString(SIZE(0..22)) ACCESS read-write STATUS mandatory DESCRIPTION "The Input #1 user-friendly name." ::= { upsmgConfigEnvironmentEntry 9 } upsmgConfigInput1ClosedLabel OBJECT-TYPE SYNTAX DisplayString(SIZE(0..18)) ACCESS read-write STATUS mandatory DESCRIPTION "The Input #1 label for closed position." ::= { upsmgConfigEnvironmentEntry 10 } upsmgConfigInput1OpenLabel OBJECT-TYPE SYNTAX DisplayString(SIZE(0..18)) ACCESS read-write STATUS mandatory DESCRIPTION "The Input #1 label for open position." ::= { upsmgConfigEnvironmentEntry 11 } upsmgConfigInput2Name OBJECT-TYPE SYNTAX DisplayString(SIZE(0..22)) ACCESS read-write STATUS mandatory DESCRIPTION "The Input #2 user-friendly name." ::= { upsmgConfigEnvironmentEntry 12 } upsmgConfigInput2ClosedLabel OBJECT-TYPE SYNTAX DisplayString(SIZE(0..18)) ACCESS read-write STATUS mandatory DESCRIPTION "The Input #2 label for closed position." ::= { upsmgConfigEnvironmentEntry 13 } upsmgConfigInput2OpenLabel OBJECT-TYPE SYNTAX DisplayString(SIZE(0..18)) ACCESS read-write STATUS mandatory DESCRIPTION "The Input #2 label for open position." ::= { upsmgConfigEnvironmentEntry 14 } -- UPS Monitoring groups of the MIB: -- upsmgBattery(5), upsmgInput(6), upsmgOutput(7), upsmgEnviron(8) ---------------------------- -- the upsmgBattery group -- ---------------------------- upsmgBatteryRemainingTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The time remaining actual charge vs actual load (dynamic)." ::= { upsmgBattery 1 } upsmgBatteryLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery level as a percentage of charge." ::= { upsmgBattery 2 } upsmgBatteryRechargeTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The actual operational battery recharge time to set point equal to upsmgConfigRechargeLevel. This value is computed from upsmgConfigRechargeLevel (level to reach), upsmgBatteryLevel (the actual reached level) and the UPS charge rate." ::= { upsmgBattery 3 } upsmgBatteryRechargeLevel OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The actual value of the battery recharge level that will be reached during the time delay necessary to restart after power returns. This value is computed from upsmgConfigRechargeTime (the delay), upsmgBatteryLevel (the actual level) and the UPS charge rate." ::= { upsmgBattery 4 } upsmgBatteryVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The actual battery voltage." ::= { upsmgBattery 5 } upsmgBatteryCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The actual battery current." ::= { upsmgBattery 6 } upsmgBatteryTemperature OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery temperature." ::= { upsmgBattery 7 } upsmgBatteryFullRechargeTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The battery full recharge time (from 0 to 100 percent) at current load." ::= { upsmgBattery 8 } upsmgBatteryFaultBattery OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The battery fault status." ::= { upsmgBattery 9 } upsmgBatteryNoBattery OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS has no Battery status." ::= { upsmgBattery 10 } upsmgBatteryReplacement OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery to be replaced status." ::= { upsmgBattery 11 } upsmgBatteryUnavailableBattery OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery is unavailable status." ::= { upsmgBattery 12 } upsmgBatteryNotHighCharge OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery quit high condition status." ::= { upsmgBattery 13 } upsmgBatteryLowBattery OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The battery low status." ::= { upsmgBattery 14 } upsmgBatteryChargerFault OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery is not charging status." ::= { upsmgBattery 15 } upsmgBatteryLowCondition OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS is at low condition status." ::= { upsmgBattery 16 } upsmgBatteryLowRecharge OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Battery is not recharged status." ::= { upsmgBattery 17 } -------------------------- -- the upsmgInput group -- -------------------------- upsmgInputPhaseNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of input phases." ::= { upsmgInput 1 } upsmgInputPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgInputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of input phases." ::= { upsmgInput 2 } upsmgInputPhaseEntry OBJECT-TYPE SYNTAX UpsmgInputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of an input phase." INDEX { mginputIndex } ::= { upsmgInputPhaseTable 1 } UpsmgInputPhaseEntry ::= SEQUENCE { -- ASN.1 type definition mginputIndex INTEGER, mginputVoltage INTEGER, mginputFrequency INTEGER, mginputMinimumVoltage INTEGER, mginputMaximumVoltage INTEGER, mginputCurrent INTEGER } mginputIndex OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "The input phase voltage index. It is a number between 1 and upsmgInputPhaseNum." ::= { upsmgInputPhaseEntry 1 } mginputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input phase voltage." ::= { upsmgInputPhaseEntry 2 } mginputFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input phase frequency." ::= { upsmgInputPhaseEntry 3 } mginputMinimumVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input phase minimum voltage over the last minute." ::= { upsmgInputPhaseEntry 4 } mginputMaximumVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input phase maximum voltage over the last minute." ::= { upsmgInputPhaseEntry 5 } mginputCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The input phase current." ::= { upsmgInputPhaseEntry 6 } upsmgInputBadStatus OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The utility power bad voltage or bad frequency status." ::= { upsmgInput 3 } upsmgInputLineFailCause OBJECT-TYPE SYNTAX INTEGER { no(1), outoftolvolt(2), outoftolfreq(3), utilityoff(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The utility power failure cause: no(1) is for no utility failure, outoftolvolt(2) is for voltage out of tolerance, outoftolfreq(3) is for frequency out of tolerance, utilityoff(4) is for no voltage at all." ::= { upsmgInput 4 } -------------------------- -- the upsmgOutput group -- -------------------------- upsmgOutputPhaseNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of output phases." ::= { upsmgOutput 1 } upsmgOutputPhaseTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgOutputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of output phases." ::= { upsmgOutput 2 } upsmgOutputPhaseEntry OBJECT-TYPE SYNTAX UpsmgOutputPhaseEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of an output phase." INDEX { mgoutputPhaseIndex } ::= { upsmgOutputPhaseTable 1 } UpsmgOutputPhaseEntry ::= SEQUENCE { -- ASN.1 type definition mgoutputPhaseIndex INTEGER, mgoutputVoltage INTEGER, mgoutputFrequency INTEGER, mgoutputLoadPerPhase INTEGER, mgoutputCurrent INTEGER } mgoutputPhaseIndex OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "The output phase voltage index. It is a number between 1 and upsmgOutputPhaseNum." ::= { upsmgOutputPhaseEntry 1 } mgoutputVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output phase voltage." ::= { upsmgOutputPhaseEntry 2 } mgoutputFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output phase frequency." ::= { upsmgOutputPhaseEntry 3 } mgoutputLoadPerPhase OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output load per phase." ::= { upsmgOutputPhaseEntry 4 } mgoutputCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output phase current." ::= { upsmgOutputPhaseEntry 5 } upsmgOutputOnBattery OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS on battery / on main status." ::= { upsmgOutput 3 } upsmgOutputOnByPass OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS on bypass status." ::= { upsmgOutput 4 } upsmgOutputUnavailableByPass OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The by pass unavailable status." ::= { upsmgOutput 5 } upsmgOutputNoByPass OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS bypass installed status." ::= { upsmgOutput 6 } upsmgOutputUtilityOff OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS utility off status." ::= { upsmgOutput 7 } upsmgOutputOnBoost OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS on booster status." ::= { upsmgOutput 8 } upsmgOutputInverterOff OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Inverter on / off status." ::= { upsmgOutput 9 } upsmgOutputOverLoad OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The output over load status." ::= { upsmgOutput 10 } upsmgOutputOverTemp OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The ups over temperature status." ::= { upsmgOutput 11 } upsmgOutputOnBuck OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS on fader status." ::= { upsmgOutput 12 } ---------------------------- -- the upsmgEnviron group -- ---------------------------- upsmgEnvironAmbientTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The ambient temperature." ::= { upsmgEnviron 1 } upsmgEnvironAmbientHumidity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The ambient humidity." ::= { upsmgEnviron 2 } upsmgEnvironExtAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgEnvironExtAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of external alarms." ::= { upsmgEnviron 3 } upsmgEnvironExtAlarmEntry OBJECT-TYPE SYNTAX UpsmgEnvironExtAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of an external alarm." INDEX { mgalarmNum } ::= { upsmgEnvironExtAlarmTable 1 } UpsmgEnvironExtAlarmEntry ::= SEQUENCE { -- ASN.1 type definition mgalarmNum INTEGER, mgalarmState INTEGER } mgalarmNum OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "The external alarm number. A number between 1 and upsmgConfigExtAlarmNum." ::= { upsmgEnvironExtAlarmEntry 1 } mgalarmState OBJECT-TYPE SYNTAX INTEGER { active(1), inactive(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The external alarm state (active or inactive)." ::= { upsmgEnvironExtAlarmEntry 2 } upsmgEnvironSensorNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The sensor unit number (0 to 4)." ::= { upsmgEnviron 4 } upsmgEnvironSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgEnvironSensorEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of sensor units." ::= { upsmgEnviron 5 } upsmgEnvironSensorEntry OBJECT-TYPE SYNTAX UpsmgEnvironSensorEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of a sensor unit." INDEX { mgsensorNum } ::= { upsmgEnvironSensorTable 1 } UpsmgEnvironSensorEntry ::= SEQUENCE { -- ASN.1 type definition mgsensorNum INTEGER, mgsensorTemp INTEGER, mgsensorHumidity INTEGER } mgsensorNum OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "The unit number. A number between 1 and 4." ::= { upsmgEnvironSensorEntry 1 } mgsensorTemp OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The measured temperature of the unit." ::= { upsmgEnvironSensorEntry 2 } mgsensorHumidity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The measured humidity of the unit." ::= { upsmgEnvironSensorEntry 3 } -- AB Release on 2003/10/23 : Add Measurements of the environment sensor. upsmgEnvironmentNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Number of Environment sensor connected." ::= { upsmgEnviron 6 } upsmgEnvironmentSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgEnvironmentSensorEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table containing the measurements and alarms made by Environment sensor units." ::= { upsmgEnviron 7 } upsmgEnvironmentSensorEntry OBJECT-TYPE SYNTAX UpsmgEnvironmentSensorEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of an entry in the measurement table." INDEX { upsmgEnvironmentIndex } ::= { upsmgEnvironmentSensorTable 1 } UpsmgEnvironmentSensorEntry ::= SEQUENCE { -- ASN.1 type definition upsmgEnvironmentIndex INTEGER, upsmgEnvironmentComFailure INTEGER, upsmgEnvironmentTemperature INTEGER, upsmgEnvironmentTemperatureLow INTEGER, upsmgEnvironmentTemperatureHigh INTEGER, upsmgEnvironmentHumidity INTEGER, upsmgEnvironmentHumidityLow INTEGER, upsmgEnvironmentHumidityHigh INTEGER, upsmgEnvironmentInput1State INTEGER, upsmgEnvironmentInput2State INTEGER } upsmgEnvironmentIndex OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "The sensor index, ranging from 1 to upsmgEnvironmentNum." ::= { upsmgEnvironmentSensorEntry 1 } upsmgEnvironmentComFailure OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The sensor communication failure : yes(1), no(2)." ::= { upsmgEnvironmentSensorEntry 2 } upsmgEnvironmentTemperature OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The temperature measurement in unit 0.1 Cel." ::= { upsmgEnvironmentSensorEntry 3 } upsmgEnvironmentTemperatureLow OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Temperature is below low theshold : yes(1), no(2)." ::= { upsmgEnvironmentSensorEntry 4 } upsmgEnvironmentTemperatureHigh OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Temperature is above high threshold : yes(1), no(2)." ::= { upsmgEnvironmentSensorEntry 5 } upsmgEnvironmentHumidity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The humidity measurement in unit 0.1 %." ::= { upsmgEnvironmentSensorEntry 6 } upsmgEnvironmentHumidityLow OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Humidity is below low threshold : yes(1), no(2)." ::= { upsmgEnvironmentSensorEntry 7 } upsmgEnvironmentHumidityHigh OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Humidity is above high threshold : yes(1), no(2)." ::= { upsmgEnvironmentSensorEntry 8 } upsmgEnvironmentInput1State OBJECT-TYPE SYNTAX INTEGER { closed(1), open(2) } ACCESS read-only STATUS mandatory DESCRIPTION "State of Input#1 : closed(1), open(2)." ::= { upsmgEnvironmentSensorEntry 9 } upsmgEnvironmentInput2State OBJECT-TYPE SYNTAX INTEGER { closed(1), open(2) } ACCESS read-only STATUS mandatory DESCRIPTION "State of Input#2 : closed(1), open(2)." ::= { upsmgEnvironmentSensorEntry 10 } -- UPS Controlling groups of the MIB: -- upsmgControl(9), upsmgTest(10), upsmgTraps(11) ---------------------------- -- the upsmgControl group -- ---------------------------- -- Receptacles control table. -- This table gives for every receptacle the ON/OFF control objects. upsmgControlReceptaclesTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsmgControlReceptaclesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The table of receptacles." ::= { upsmgControl 1 } upsmgControlReceptaclesEntry OBJECT-TYPE SYNTAX UpsmgControlReceptaclesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The description of a receptacle entry in the table." INDEX { mgreceptacleIndexc } ::= { upsmgControlReceptaclesTable 1 } UpsmgControlReceptaclesEntry ::= SEQUENCE { -- ASN.1 type definition mgreceptacleIndexc INTEGER, mgreceptacleOnDelay INTEGER, mgreceptacleOnCtrl INTEGER, mgreceptacleOnStatus INTEGER, mgreceptacleOffDelay INTEGER, mgreceptacleOffCtrl INTEGER, mgreceptacleOffStatus INTEGER, mgreceptacleToggleDelay INTEGER, mgreceptacleToggleCtrl INTEGER, mgreceptacleToggleStatus INTEGER, mgreceptacleToggleDuration INTEGER } mgreceptacleIndexc OBJECT-TYPE SYNTAX INTEGER (1..50) ACCESS read-only STATUS mandatory DESCRIPTION "A unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum." ::= { upsmgControlReceptaclesEntry 1 } mgreceptacleOnDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Turn on UPS receptacle w/delay=?." ::= { upsmgControlReceptaclesEntry 2 } mgreceptacleOnCtrl OBJECT-TYPE SYNTAX INTEGER { nothing(1), start(2), stop(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The receptacle control on action." ::= { upsmgControlReceptaclesEntry 3 } mgreceptacleOnStatus OBJECT-TYPE SYNTAX INTEGER { none(1), started(2), inprogressinups(3), completed(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The receptacle control on status." ::= { upsmgControlReceptaclesEntry 4 } mgreceptacleOffDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Turn off UPS receptacle w/delay=?." ::= { upsmgControlReceptaclesEntry 5 } mgreceptacleOffCtrl OBJECT-TYPE SYNTAX INTEGER { nothing(1), start(2), stop(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The receptacle control off action." ::= { upsmgControlReceptaclesEntry 6 } mgreceptacleOffStatus OBJECT-TYPE SYNTAX INTEGER { none(1), started(2), inprogressinups(3), completed(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The receptacle control off status." ::= { upsmgControlReceptaclesEntry 7 } mgreceptacleToggleDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Turn off then on UPS receptacle w/delay=?." ::= { upsmgControlReceptaclesEntry 8 } mgreceptacleToggleCtrl OBJECT-TYPE SYNTAX INTEGER { nothing(1), start(2), stop(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The receptacle control toggle action." ::= { upsmgControlReceptaclesEntry 9 } mgreceptacleToggleStatus OBJECT-TYPE SYNTAX INTEGER { none(1), started(2), inprogressinups(3), completed(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The receptacle control toggle status." ::= { upsmgControlReceptaclesEntry 10 } mgreceptacleToggleDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Turn off then on UPS receptacle w/duration=?." ::= { upsmgControlReceptaclesEntry 11 } upsmgControlDayOff OBJECT-TYPE SYNTAX INTEGER { sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saterday(7), none(8) } ACCESS read-write STATUS mandatory DESCRIPTION "The schedule off control object. Default value is none(8). Value 1 means to start scheduled off on Sunday, value 2 to start scheduled off on Monday, and so on." ::= { upsmgControl 2 } upsmgControlDayOn OBJECT-TYPE SYNTAX INTEGER { sunday(1), monday(2), tuesday(3), wednesday(4), thursday(5), friday(6), saterday(7), none(8) } ACCESS read-write STATUS mandatory DESCRIPTION "The schedule on control object. Default value is none(8). Value 1 means to start scheduled on on Sunday, value 2 to start scheduled on on Monday, and so on. This object is meaningfull only for those agent that do not include internal clock. In such a case the object is set by a manager to start the schedule on sequence." ::= { upsmgControl 3 } -------------------------- -- the upsmgTest group -- -------------------------- upsmgTestBatterySchedule OBJECT-TYPE SYNTAX INTEGER { unknown(1), weekly(2), monthly(3), atturnon(4), none(5), dayly(6) } ACCESS read-write STATUS mandatory DESCRIPTION "The automatic battery test schedule." ::= { upsmgTest 1 } upsmgTestDiagnostics OBJECT-TYPE SYNTAX INTEGER { default(1), start(2) } ACCESS read-write STATUS mandatory DESCRIPTION "To run self test diagnostics." ::= { upsmgTest 2 } upsmgTestDiagResult OBJECT-TYPE SYNTAX INTEGER { success(1), failed(2), none(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The automatic test diagnostic result." ::= { upsmgTest 3 } upsmgTestBatteryCalibration OBJECT-TYPE SYNTAX INTEGER { default(1), start(2) } ACCESS read-write STATUS mandatory DESCRIPTION "To run battery test calibration." ::= { upsmgTest 4 } upsmgTestLastCalibration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The last battery calibration test date." ::= { upsmgTest 5 } upsmgTestIndicators OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "To run UPS indicators test." ::= { upsmgTest 6 } upsmgTestCommandLine OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "To send ASCII command line to UPS." ::= { upsmgTest 7 } upsmgTestCommandReady OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "To advise UPS that command line has been prepared." ::= { upsmgTest 8 } upsmgTestResponseLine OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "To get ASCII protocol response from UPS." ::= { upsmgTest 9 } upsmgTestResponseReady OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS mandatory DESCRIPTION "To advise agent that response line has been received." ::= { upsmgTest 10 } upsmgTestBatteryResult OBJECT-TYPE SYNTAX INTEGER { msuccess(1), mfailed(2), ssuccess(3), sfailed(4), none(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The test battery result: msuccess(1) is for manual battery test success, ssuccess(3) is for scheduled battery test success, mfailed(2) is for manual battery test failed, sfailed(4) is for scheduled battery test failed." ::= { upsmgTest 11 } -------------------------- -- the upsmgTraps group -- -------------------------- -- This group defines objects and traps, so that for each trap, simple -- get request on related objects (one or many) allow to confirm actual -- status of the trap. -- TRAPS NOTIFICATIONS upsmgBatteryFault TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS Battery entering Fault status." --#SEVERITY MAJOR ::= 1 upsmgBatteryOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS Battery returned to OK status." --#SEVERITY INFORMATIONAL ::= 2 upsmgBatteryReplacementIndicated TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS battery need to be replaced." --#SEVERITY MINOR ::= 3 upsmgBatteryReplaceNotIndicated TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS battery does not need to be replaced." --#SEVERITY INFORMATIONAL ::= 4 upsmgAtLowBattery TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel } DESCRIPTION "Trap UPS battery reached low condition." --#SEVERITY CRITICAL ::= 5 upsmgFromLowBattery TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel } DESCRIPTION "Trap UPS battery returned from low condition." --#SEVERITY INFORMATIONAL ::= 6 upsmgChargerFault TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS battery charger is not active." --#SEVERITY MINOR ::= 7 upsmgChargerOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS battery charger is active." --#SEVERITY INFORMATIONAL ::= 8 upsmgAtLowCondition TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel } DESCRIPTION "Trap UPS entering low condition." --#SEVERITY CRITICAL ::= 9 upsmgFromLowCondition TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel } DESCRIPTION "Trap UPS exiting low condition." --#SEVERITY INFORMATIONAL ::= 10 upsmgOnBattery TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel } DESCRIPTION "Trap UPS is on Battery." --#SEVERITY CRITICAL ::= 11 upsmgReturnFromBattery TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel } DESCRIPTION "Trap UPS returned from battery." --#SEVERITY INFORMATIONAL ::= 12 upsmgOnByPass TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS is on by pass." --#SEVERITY MAJOR ::= 13 upsmgReturnFromByPass TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS return from by pass." --#SEVERITY INFORMATIONAL ::= 14 upsmgByPassUnavailable TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS by pass unavailable." --#SEVERITY MINOR ::= 15 upsmgByPassAvailable TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS by pass available." --#SEVERITY INFORMATIONAL ::= 16 upsmgUtilityFailure TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS utility power failed." --#SEVERITY MAJOR ::= 17 upsmgUtilityRestored TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS utility power restored." --#SEVERITY INFORMATIONAL ::= 18 upsmgOnBoost TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS is on boost." --#SEVERITY MINOR ::= 19 upsmgReturnFromBoost TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS has returned from boost." --#SEVERITY INFORMATIONAL ::= 20 upsmgOverLoad TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS has overload condition." --#SEVERITY MAJOR ::= 21 upsmgLoadOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS quit overload condition." --#SEVERITY INFORMATIONAL ::= 22 upsmgOverTemperature TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS has overtemperature condition." --#SEVERITY MAJOR ::= 23 upsmgTemperatureOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS quit overtemperature condition." --#SEVERITY INFORMATIONAL ::= 24 upsmgOnToStart TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleState, mgreceptacleOnDelay, mgreceptacleRestartDelay } DESCRIPTION "Trap UPS on sequence started." --#SEVERITY MAJOR ::= 25 upsmgOnAbort TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleOnDelay } DESCRIPTION "Trap UPS on sequence cancelled." --#SEVERITY INFORMATIONAL ::= 26 upsmgOnInProgress TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleState, mgreceptacleBootUpDuration } DESCRIPTION "Trap UPS on sequence in progress in ups." --#SEVERITY CRITICAL ::= 27 upsmgOnComplete TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleOnDelay } DESCRIPTION "Trap UPS on sequence completed." --#SEVERITY INFORMATIONAL ::= 28 upsmgOffToStart TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleState, mgreceptacleOffDelay, mgreceptacleShutoffTimer, upsmgConfigSysShutDuration } DESCRIPTION "Trap UPS off sequence started." --#SEVERITY MAJOR ::= 29 upsmgOffAbort TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleOffDelay } DESCRIPTION "Trap UPS off sequence cancelled." --#SEVERITY INFORMATIONAL ::= 30 upsmgOffInProgress TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleState, mgreceptacleShutdownDuration } DESCRIPTION "Trap UPS off sequence in progress in ups." --#SEVERITY CRITICAL ::= 31 upsmgOffComplete TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleOffDelay } DESCRIPTION "Trap UPS off sequence completed." --#SEVERITY INFORMATIONAL ::= 32 upsmgToggleToStart TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleToggleDelay } DESCRIPTION "Trap UPS toggle (off/on) sequence started." --#SEVERITY MAJOR ::= 33 upsmgToggleAbort TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleToggleDelay } DESCRIPTION "Trap UPS toggle (off/on) sequence cancelled." --#SEVERITY INFORMATIONAL ::= 34 upsmgToggleInProgress TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleToggleDuration } DESCRIPTION "Trap UPS toggle (off/on) sequence in progress in ups." --#SEVERITY MAJOR ::= 35 upsmgToggleComplete TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgreceptacleIndex, mgreceptacleToggleDuration } DESCRIPTION "Trap UPS toggle (off/on) sequence completed." --#SEVERITY INFORMATIONAL ::= 36 upsmgCommunicationFailure TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS serial communication failed." --#SEVERITY CRITICAL ::= 37 upsmgCommunicationRestored TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS serial communication restored." --#SEVERITY INFORMATIONAL ::= 38 upsmgInputBad TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS input has bad condition." --#SEVERITY MINOR ::= 39 upsmgInputOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS input quit bad condition." --#SEVERITY INFORMATIONAL ::= 40 upsmgBatteryUnavailable TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS battery is unavailable." --#SEVERITY MINOR ::= 41 upsmgBatteryAvailable TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS battery return from unavailable condition." --#SEVERITY INFORMATIONAL ::= 42 upsmgAtLowRecharge TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel } DESCRIPTION "Trap UPS waiting for battery charging condition." --#SEVERITY INFORMATIONAL ::= 43 upsmgFromLowRecharge TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel } DESCRIPTION "Trap UPS reached battery charging condition." --#SEVERITY INFORMATIONAL ::= 44 upsmgDiagnosticTestFail TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS self test failed." --#SEVERITY MINOR ::= 45 upsmgDiagnosticTestOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS self test succeeded." --#SEVERITY INFORMATIONAL ::= 46 upsmgBatteryTestOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS passed battery test." --#SEVERITY INFORMATIONAL ::= 47 upsmgBatteryTestFail TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS failed battery test." --#SEVERITY MAJOR ::= 48 upsmgExternalAlarmActive TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgextAlarmIndex, mgextAlarmUID } DESCRIPTION "Trap UPS enter environment external alarm." --#SEVERITY MAJOR ::= 49 upsmgExternalAlarmInactive TRAP-TYPE ENTERPRISE upsmgTraps VARIABLES { mgextAlarmIndex, mgextAlarmUID } DESCRIPTION "Trap UPS exit environment external alarm." --#SEVERITY INFORMATIONAL ::= 50 upsmgOnBuck TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS is on buck." --#SEVERITY MINOR ::= 51 upsmgReturnFromBuck TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Trap UPS has returned from buck." --#SEVERITY INFORMATIONAL ::= 52 -- AB Release on 2003/10/23 : Traps 53 to 64 added for the environment sensor. upsmgEnvironComFailure TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Environment Probe communication failure." --#SEVERITY MAJOR ::= 53 upsmgEnvironComOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Environment Probe communication restored." --#SEVERITY INFORMATIONAL ::= 54 upsmgEnvironTemperatureLow TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Temperature is below low threshold." --#SEVERITY MAJOR ::= 55 upsmgEnvironTemperatureHigh TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Temperature is above high threshold." --#SEVERITY MAJOR ::= 56 upsmgEnvironTemperatureOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Temperature is in normal range." --#SEVERITY INFORMATIONAL ::= 57 upsmgEnvironHumidityLow TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Humidity is below low threshold." --#SEVERITY MAJOR ::= 58 upsmgEnvironHumidityHigh TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Humidity is above high threshold." --#SEVERITY MAJOR ::= 59 upsmgEnvironHumidityOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Humidity is in normal range." --#SEVERITY INFORMATIONAL ::= 60 upsmgEnvironInput1Closed TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Input #1 is Closed." --#SEVERITY INFORMATIONAL ::= 61 upsmgEnvironInput1Open TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Input #1 is Open." --#SEVERITY INFORMATIONAL ::= 62 upsmgEnvironInput2Closed TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Input #2 is Closed." --#SEVERITY INFORMATIONAL ::= 63 upsmgEnvironInput2Open TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Input #2 is Open." --#SEVERITY INFORMATIONAL ::= 64 -- AD Release on 2006/12/19 : Traps 65 and 66 added about redundancy. upsRedundancyLost TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Redundancy Lost." --#SEVERITY MAJOR ::= 65 upsRedundancyOK TRAP-TYPE ENTERPRISE upsmgTraps DESCRIPTION "Redundancy Recovered." --#SEVERITY INFORMATIONAL ::= 66 ---------------------- -- upsmgAgent group -- ---------------------- -- following objects are configuration variables defined for -- UPS proxy agent that perform UPS management protocol -- and support SNMP management function upsmgAgentIpaddress OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION " The ip address that NMS can identify the managed device" ::= { upsmgAgent 1} upsmgAgentSubnetMask OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION " Internet address subnet mask" ::= { upsmgAgent 2} upsmgAgentDefGateway OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION " The default gateway that allow device managed through routers " ::= { upsmgAgent 3} upsmgAgentBaudRate OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION " the serial port communication speed. only 2400, 4800, and 9600 allowed" ::= { upsmgAgent 4} upsmgAgentPollRate OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION " The frequency that proxy agent polls the connected UPS in ASCII protocol. (unit : second)" ::= { upsmgAgent 5} upsmgAgentType OBJECT-TYPE SYNTAX INTEGER { deviceEth(1), deviceTR(2), proxyEth(3), proxyTR(4), other(5) } ACCESS read-write STATUS mandatory DESCRIPTION " The type of agent." ::= { upsmgAgent 6} upsmgAgentTrapAlarmDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION " The interval for the Trap packet retransmission, while the TRAP Acknowledge is implemented and the ack is received within the interval." ::= { upsmgAgent 7} upsmgAgentTrapAlarmRetry OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION " The retry count for retransmitting Trap packet while the TRAP acknowledge is implemented." ::= { upsmgAgent 8} upsmgAgentReset OBJECT-TYPE SYNTAX INTEGER { reset (1), nothing(2) } ACCESS read-write STATUS mandatory DESCRIPTION " The variable initiates reset operation in agent software, ie. warm start. write reset(1) to any one of UPS MIB array, will result in the same reset operation." ::= { upsmgAgent 9} upsmgAgentFactReset OBJECT-TYPE SYNTAX INTEGER { reset (1), nothing(2) } ACCESS read-write STATUS mandatory DESCRIPTION " The variable initiates reset operation in agent software, ie. warm start, and load default data (Factory setting) to EEPROM and to runtime parameters associated with the UPS." ::= { upsmgAgent 10} upsmgAgentMibVersion OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION " The version of the MIB implemented in agent." ::= { upsmgAgent 11} upsmgAgentFirmwareVersion OBJECT-TYPE SYNTAX DisplayString(SIZE(0..32)) ACCESS read-only STATUS mandatory DESCRIPTION " The agent firmware version." ::= { upsmgAgent 12} upsmgAgentCommUPS OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION " The status of communication between agent and ups. Even value means no communication, and odd value means a certain level of communication with devices daisy-chained on the serial port. The value is the following: 1000*NSE + 100*NSW + 10*UPSW + UPST with UPST is UPS type: 5 if no UPS; 3 if PI (Protocol Interface) 1 if U-Talk UPS; UPSW is the number of switchable plugs of the UPS; NSW is the number of UM-Switch devices; NSE is the number of UM-Sensor devices." ::= { upsmgAgent 13} upsmgAgentTrapAck OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION " The last Trap number that has been received by UM-View." ::= { upsmgAgent 14} upsmgAgentAutoLearning OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION " The enabled/disabled configuration of the Auto Learning process of the agent, default value is yes(1) e.g. enabled." ::= { upsmgAgent 15} upsmgAgentBootP OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION " The enabled/disabled configuration of the BootP process, default value is yes(1) e.g. enabled." ::= { upsmgAgent 16} upsmgAgentTFTP OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION " The enabled/disabled configuration of the TFTP process, default value is no(2) e.g. disabled." ::= { upsmgAgent 17} upsmgAgentTrapSignature OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION " The signature of the trap acknowledged by a manager." ::= { upsmgAgent 18} ------------------------ -- upsmgRemote group -- ------------------------ upsmgRemoteOnBattery OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "An object to inform an ups-less agent that the remote UPS is on autonomy. This object could be set by a management application." ::= { upsmgRemote 1} upsmgRemoteIpAddress OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "An object to give the IP address of the agent managing the remote UPS. This object could be read by managers to perform management of receptacle dependencies between two different agents." ::= { upsmgRemote 2} END