-- Title: LIEB_MIC.MIB -- Version: v1.0 -- Date: 05/30/95 10:45am -- -- Copyright @ 1995 Liebert Corporation. All rights reserved worldwide. -- -- This MIB defines the objects for the Liebert Micro UPS SNMP Agent. -- LIEBERT-MICRO-UPS-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises, TimeTicks, Gauge FROM RFC1155-SMI OBJECT-TYPE FROM RFC-1212 sysUpTime, DisplayString FROM RFC1213-MIB TRAP-TYPE FROM RFC-1215; emerson OBJECT IDENTIFIER ::= { enterprises 476 } -- -- Divisions of Emerson -- liebertCorp OBJECT IDENTIFIER ::= { emerson 1 } -- -- Areas of Liebert Corporation -- liebertUps OBJECT IDENTIFIER ::= { liebertCorp 1 } -- -- UPS -- luExtensions OBJECT IDENTIFIER ::= { liebertUps 1 } luExperimental OBJECT IDENTIFIER ::= { liebertUps 2 } luPrivate OBJECT IDENTIFIER ::= { liebertUps 3 } -- -- UPS Extensions -- luCore OBJECT IDENTIFIER ::= { luExtensions 1 } -- -- The Device Identification group. -- All objects in this group are determined at device -- initialization and remain static. -- lcUpsIdent OBJECT IDENTIFIER ::= { luCore 1 } lcUpsIdentManufacturer OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) ACCESS read-only STATUS optional DESCRIPTION "The UPS manufacturer." ::= { lcUpsIdent 1 } lcUpsIdentModel OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) ACCESS read-write STATUS optional DESCRIPTION "The UPS Model designation." ::= { lcUpsIdent 2 } lcUpsIdentSoftwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) ACCESS read-only STATUS optional DESCRIPTION "The UPS SNMP Agent software version." ::= { lcUpsIdent 3 } lcUpsIdentSpecific OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS optional DESCRIPTION "A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value." ::= { lcUpsIdent 4 } -- -- The Alarm group. -- lcUpsAlarm OBJECT IDENTIFIER ::= { luCore 6 } lcUpsAlarms OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS optional DESCRIPTION "The current number of alarm conditions." ::= { lcUpsAlarm 1 } lcUpsAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF LcUpsAlarmEntry ACCESS not-accessible STATUS optional ::= { lcUpsAlarm 2 } lcUpsAlarmEntry OBJECT-TYPE SYNTAX LcUpsAlarmEntry ACCESS not-accessible STATUS optional INDEX { lcUpsAlarmId } ::= { lcUpsAlarmTable 1 } LcUpsAlarmEntry ::= SEQUENCE { lcUpsAlarmId INTEGER, lcUpsAlarmDescr OBJECT IDENTIFIER, lcUpsAlarmTime TimeTicks } lcUpsAlarmId OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-only STATUS optional DESCRIPTION "A unique identifier for an alarm condition. This value must remain constant between agent initializations." ::= { lcUpsAlarmEntry 1 } lcUpsAlarmDescr OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS optional DESCRIPTION "A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition." ::= { lcUpsAlarmEntry 2 } lcUpsAlarmTime OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS optional DESCRIPTION "The value of sysUpTime when the alarm condition occured." ::= { lcUpsAlarmEntry 3 } -- -- Well known alarm condtions. -- lcUpsAlarmConditions OBJECT IDENTIFIER ::= { lcUpsAlarm 3 } lcUpsAlarmLowBatteryWarning OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 1 } -- Battery capacity is low. lcUpsAlarmOnBattery OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 10 } -- The UPS is running on battery. lcUpsAlarmStopNoticeIssued OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 11 } -- The UPS has been told to discontinue output. -- -- The Control group. -- lcUpsControl OBJECT IDENTIFIER ::= { luCore 8 } lcUpsControlUnixShutdownDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'." ::= { lcUpsControl 5 } lcUpsControlUnixShutdownTrapDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0." ::= { lcUpsControl 6 } lcUpsControlCancelCommands OBJECT-TYPE SYNTAX INTEGER { unknown (1), cancel (2) } ACCESS read-write STATUS optional DESCRIPTION "Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown." ::= { lcUpsControl 7 } lcUpsControlRebootAgentDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel." ::= { lcUpsControl 8 } -- -- The Nominal group. -- lcUpsNominal OBJECT IDENTIFIER ::= { luCore 9 } lcUpsNominalOutputVoltage OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal output voltage. (Unit of measure: volt)" ::= { lcUpsNominal 1 } lcUpsNominalInputVoltage OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal input voltage. (Unit of measure: volt)" ::= { lcUpsNominal 2 } lcUpsNominalOutputVA OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal Volt-Amp rating." ::= { lcUpsNominal 3 } lcUpsNominalOutputWatts OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal power rating. (Unit of measure: watt)" ::= { lcUpsNominal 4 } lcUpsNominalOutputFreq OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal output frequency. (Unit of measure: Hertz)" ::= { lcUpsNominal 5 } lcUpsNominalInputFreq OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal input frequency. (Unit of measure: Hertz)" ::= { lcUpsNominal 6 } -- -- The Core Liebert UPS traps -- lcUpsTraps OBJECT IDENTIFIER ::= { luCore 11 } lcUpsOnBatteryTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power." ::= 3 lcUpsLowBatteryWarningTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state." ::= 4 lcUpsAlarmTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An Alarm condition has occurred and is being reported in the lcUpsAlarmTable." ::= 11 lcUpsUnixShutdownTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown." ::= 16 lcUpsUnixShutdownWarningTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay." ::= 17 -- -- The Proxy/MicroUPS Extension -- luExternal OBJECT IDENTIFIER ::= { luExtensions 6 } END