-- Title: LIEB_43C.MIB -- Version: v1.0 -- Date: 07/22/96 02:00pm -- -- Copyright @ 1996 Liebert Corporation. All rights reserved worldwide. -- -- This MIB defines objects for the Liebert AP4300 SNMP Agents. -- LIEBERT-SERIES-4300-UPS-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises, Counter, TimeTicks, Gauge FROM RFC1155-SMI OBJECT-TYPE FROM RFC-1212 sysUpTime, DisplayString FROM RFC1213-MIB TRAP-TYPE FROM RFC-1215; emerson OBJECT IDENTIFIER ::= { enterprises 476 } -- -- Divisions of Emerson -- liebertCorp OBJECT IDENTIFIER ::= { emerson 1 } -- -- Areas of Liebert Corporation -- liebertUps OBJECT IDENTIFIER ::= { liebertCorp 1 } -- -- UPS -- luExtensions OBJECT IDENTIFIER ::= { liebertUps 1 } luExperimental OBJECT IDENTIFIER ::= { liebertUps 2 } luPrivate OBJECT IDENTIFIER ::= { liebertUps 3 } -- -- UPS Extensions -- luCore OBJECT IDENTIFIER ::= { luExtensions 1 } -- -- The Device Identification group. -- All objects in this group are determined at device -- initialization and remain static. -- lcUpsIdent OBJECT IDENTIFIER ::= { luCore 1 } lcUpsIdentManufacturer OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) ACCESS read-only STATUS optional DESCRIPTION "The UPS manufacturer." ::= { lcUpsIdent 1 } lcUpsIdentModel OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) ACCESS read-write STATUS optional DESCRIPTION "The UPS Model designation." ::= { lcUpsIdent 2 } lcUpsIdentSoftwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) ACCESS read-only STATUS optional DESCRIPTION "The UPS SNMP Agent software version." ::= { lcUpsIdent 3 } lcUpsIdentSpecific OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS optional DESCRIPTION "A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value." ::= { lcUpsIdent 4 } -- -- The Battery group. -- lcUpsBattery OBJECT IDENTIFIER ::= { luCore 2 } lcUpsBatTimeRemaining OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS optional DESCRIPTION "The estimated time to depletion of battery charge. (Unit of measure: Minute)" ::= { lcUpsBattery 1 } lcUpsBatTemperature OBJECT-TYPE SYNTAX INTEGER (-32768..32767) ACCESS read-only STATUS optional DESCRIPTION "The battery temperature. (Unit of measure: Degree, Centigrade)" ::= { lcUpsBattery 2 } lcUpsBatVoltage OBJECT-TYPE SYNTAX INTEGER (-32768..32767) ACCESS read-only STATUS optional DESCRIPTION "The current battery voltage. (Unit of measure: volt)" ::= { lcUpsBattery 3 } lcUpsBatCapacity OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-only STATUS optional DESCRIPTION "The current battery capacity in percentage of total available." ::= { lcUpsBattery 6 } -- -- The Output group. -- lcUpsOutput OBJECT IDENTIFIER ::= { luCore 4 } lcUpsOutputFrequency OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-only STATUS optional DESCRIPTION "The current output frequency. (Unit of measure: Hertz)" ::= { lcUpsOutput 1 } lcUpsOutputLoad OBJECT-TYPE SYNTAX INTEGER (0..100) ACCESS read-only STATUS optional DESCRIPTION "The current output load percentage." ::= { lcUpsOutput 2 } lcUpsOutputNumLines OBJECT-TYPE SYNTAX INTEGER (1..3) ACCESS read-only STATUS optional DESCRIPTION "The number of output lines utilized in this device. This entry indicates the number of rows in the output table." ::= { lcUpsOutput 3 } lcUpsOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF LcUpsOutputEntry ACCESS not-accessible STATUS optional ::= { lcUpsOutput 4 } lcUpsOutputEntry OBJECT-TYPE SYNTAX LcUpsOutputEntry ACCESS not-accessible STATUS optional INDEX { lcUpsOutputLine } ::= { lcUpsOutputTable 1 } LcUpsOutputEntry ::= SEQUENCE { lcUpsOutputLine INTEGER, lcUpsOutputVoltage INTEGER, lcUpsOutputCurrent INTEGER, lcUpsOutputVA INTEGER } lcUpsOutputLine OBJECT-TYPE SYNTAX INTEGER (1..3) ACCESS read-only STATUS optional DESCRIPTION "The output Line." ::= { lcUpsOutputEntry 1 } lcUpsOutputVoltage OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-only STATUS optional DESCRIPTION "The output voltage. (Unit of measure: Volt)" ::= { lcUpsOutputEntry 2 } lcUpsOutputCurrent OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-only STATUS optional DESCRIPTION "The output current. (Unit of measure: Amp)" ::= { lcUpsOutputEntry 3 } lcUpsOutputVA OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-only STATUS optional DESCRIPTION "The output volt-amps." ::= { lcUpsOutputEntry 4 } lcUpsOutputWatts OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-only STATUS optional DESCRIPTION "The output power in watts." ::= { lcUpsOutput 5 } -- -- The Inverter group. -- lcUpsInverter OBJECT IDENTIFIER ::= { luCore 5 } lcUpsInverterStatus OBJECT-TYPE SYNTAX INTEGER { unknown (1), on (2), off (3) } ACCESS read-only STATUS optional DESCRIPTION "The state of the inverter. Unknown is returned if the state can not be determined." ::= { lcUpsInverter 1 } lcUpsInverterTemp OBJECT-TYPE SYNTAX INTEGER (-32768..32767) ACCESS read-only STATUS optional DESCRIPTION "The temperature of the inverter. (Unit of measure: degree, Centigrade)" ::= { lcUpsInverter 2 } -- -- The Alarm group. -- lcUpsAlarm OBJECT IDENTIFIER ::= { luCore 6 } lcUpsAlarms OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS optional DESCRIPTION "The current number of alarm conditions." ::= { lcUpsAlarm 1 } lcUpsAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF LcUpsAlarmEntry ACCESS not-accessible STATUS optional ::= { lcUpsAlarm 2 } lcUpsAlarmEntry OBJECT-TYPE SYNTAX LcUpsAlarmEntry ACCESS not-accessible STATUS optional INDEX { lcUpsAlarmId } ::= { lcUpsAlarmTable 1 } LcUpsAlarmEntry ::= SEQUENCE { lcUpsAlarmId INTEGER, lcUpsAlarmDescr OBJECT IDENTIFIER, lcUpsAlarmTime TimeTicks } lcUpsAlarmId OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-only STATUS optional DESCRIPTION "A unique identifier for an alarm condition. This value must remain constant between agent initializations." ::= { lcUpsAlarmEntry 1 } lcUpsAlarmDescr OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS optional DESCRIPTION "A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition." ::= { lcUpsAlarmEntry 2 } lcUpsAlarmTime OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS optional DESCRIPTION "The value of sysUpTime when the alarm condition occured." ::= { lcUpsAlarmEntry 3 } -- -- Well known alarm condtions. -- lcUpsAlarmConditions OBJECT IDENTIFIER ::= { lcUpsAlarm 3 } lcUpsAlarmLowBatteryWarning OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 1 } -- Battery capacity is low. lcUpsAlarmLowBatteryShutdown OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 2 } -- Battery capacity is low and has caused the UPS to shutdown. lcUpsAlarmUtilFailed OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 3 } -- Input line has lost power lcUpsAlarmOverTempWarning OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 4 } -- An excessive temperature condition has been detected. lcUpsAlarmOverTempShutdown OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 5 } -- An excessive temperature condition has caused the UPS -- to shutdown. lcUpsAlarmOutputOverloadWarning OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 6 } -- An overload condition on the output has been detected. lcUpsAlarmOutputOverloadShutdown OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 7 } -- An overload condition on the output has been detected and -- caused the UPS to shutdown. lcUpsAlarmInputOverVoltage OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 8 } -- An voltage above nominal limits has been detected on an Input -- line. lcUpsAlarmBatteryBad OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 9 } -- The UPS has detected that the battery is bad. lcUpsAlarmOnBattery OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 10 } -- The UPS is running on battery. lcUpsAlarmStopNoticeIssued OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 11 } -- The UPS has been told to discontinue output. lcUpsAlarmUpsOff OBJECT IDENTIFIER ::= { lcUpsAlarmConditions 12 } -- The UPS Inverter and bypass are both off. -- -- The Test group -- testXYZ - Initiates test of the XYZ function. -- testXYZStatus - An enumerated value indicating test results -- -- lcUpsTest OBJECT IDENTIFIER ::= { luCore 7 } lcUpsTestBattery OBJECT-TYPE SYNTAX INTEGER { unknown (1), start (2), abort (3) } ACCESS read-write STATUS optional DESCRIPTION "Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. If 'lcUpsTestBatteryStatus' is 'failed' the test may not be performed again and the status will remain in the failure state." ::= { lcUpsTest 1 } lcUpsTestBatteryStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), passed(2), failed(3), inProgress(4), sysFailure(5), notSupported(6), inhibited(7) } ACCESS read-only STATUS optional DESCRIPTION "The status of the battery test." ::= { lcUpsTest 2 } lcUpsTestDiag OBJECT-TYPE SYNTAX INTEGER { unknown (1), start (2), abort (3) } ACCESS read-write STATUS optional DESCRIPTION "Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'." ::= { lcUpsTest 3 } lcUpsTestDiagStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), passed(2), failed(3), inProgress(4), sysFailure(5), notSupported(6), inhibited(7) } ACCESS read-only STATUS optional DESCRIPTION "The status of the diagnostics test." ::= { lcUpsTest 4 } -- -- The Control group. -- lcUpsControl OBJECT IDENTIFIER ::= { luCore 8 } lcUpsControlOutputOffDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel." ::= { lcUpsControl 1 } lcUpsControlOutputOnDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel." ::= { lcUpsControl 2 } lcUpsControlOutputOffTrapDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0." ::= { lcUpsControl 3 } lcUpsControlOutputOnTrapDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will be reset to 0." ::= { lcUpsControl 4 } lcUpsControlUnixShutdownDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'." ::= { lcUpsControl 5 } lcUpsControlUnixShutdownTrapDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0." ::= { lcUpsControl 6 } lcUpsControlCancelCommands OBJECT-TYPE SYNTAX INTEGER { unknown (1), cancel (2) } ACCESS read-write STATUS optional DESCRIPTION "Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown." ::= { lcUpsControl 7 } lcUpsControlRebootAgentDelay OBJECT-TYPE SYNTAX INTEGER (0..2147483647) ACCESS read-write STATUS optional DESCRIPTION "Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel." ::= { lcUpsControl 8 } -- -- The Nominal group. -- lcUpsNominal OBJECT IDENTIFIER ::= { luCore 9 } lcUpsNominalOutputVoltage OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal output voltage. (Unit of measure: volt)" ::= { lcUpsNominal 1 } lcUpsNominalInputVoltage OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal input voltage. (Unit of measure: volt)" ::= { lcUpsNominal 2 } lcUpsNominalOutputVA OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal Volt-Amp rating." ::= { lcUpsNominal 3 } lcUpsNominalOutputFreq OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal output frequency. (Unit of measure: Hertz)" ::= { lcUpsNominal 5 } lcUpsNominalInputFreq OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-write STATUS optional DESCRIPTION "The nominal input frequency. (Unit of measure: Hertz)" ::= { lcUpsNominal 6 } -- -- The Core Liebert UPS traps -- lcUpsTraps OBJECT IDENTIFIER ::= { luCore 11 } lcUpsOverloadWarningTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOverloadWarningTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity." ::= 1 lcUpsOverloadShutdownTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOverloadShutdownTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity and has shut off the output." ::= 2 lcUpsOnBatteryTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power." ::= 3 lcUpsLowBatteryWarningTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state." ::= 4 lcUpsLowBatteryShutdownTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsLowBatteryShutdownTrap signifies that the UPS has shut off the output due to a Low Battery state." ::= 5 lcUpsUtilPowerFailedTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsUtilPowerFailedTrap signifies that the utility power input to the UPS has been lost." ::= 6 lcUpsUtilPowerRestoredTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsUtilPowerRestoredTrap signifies that the utility power has been restored to the UPS." ::= 7 lcUpsInputOverVoltageTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsInputOverVoltageTrap signifies that the UPS has detected a high input voltage condition." ::= 8 lcUpsOverTempWarningTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOverTempWarningTrap signifies that the UPS has detected a excessive temperature condition." ::= 9 lcUpsOverTempShutdownTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOverTempShutdownTrap signifies that the UPS has detected a excessive temperature condition and shut off the output." ::= 10 lcUpsAlarmTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An Alarm condition has occurred and is being reported in the lcUpsAlarmTable." ::= 11 lcUpsOutputOffTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOutputOffTrap is sent when the UPS turns all of its output off, either at the inverter or via a relay." ::= 12 lcUpsOutputOffWarningTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOutputOffWarningTrap is sent when the lcUpsControlOutputOffDelay reaches the value of lcUpsControlOutputOffTrapDelay." ::= 13 lcUpsOutputOnTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOutputOnTrap is sent when the UPS turns all of its output back on, either at the inverter or via a relay." ::= 14 lcUpsOutputOnWarningTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsOutputOnWarningTrap is sent when the lcUpsControlOutputOnDelay reaches the value of lcUpsControlOutputOnTrapDelay." ::= 15 lcUpsUnixShutdownTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown." ::= 16 lcUpsUnixShutdownWarningTrap TRAP-TYPE ENTERPRISE lcUpsTraps VARIABLES { sysUpTime } DESCRIPTION "An lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay." ::= 17 -- -- The Series 4300 Extension -- luSeries4300 OBJECT IDENTIFIER ::= { luExtensions 10 } -- -- The Liebert Series 4300 UPS Ident group. -- ls43cUpsIdent OBJECT IDENTIFIER ::= { luSeries4300 1 } ls43cUpsIdentFirmwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (255)) ACCESS read-only STATUS optional DESCRIPTION "The firmware revision level of the UPS." ::= { ls43cUpsIdent 1 } -- -- The Liebert Series 4300 UPS Configuration group. -- ls43cUpsConfig OBJECT IDENTIFIER ::= { luSeries4300 12 } ls43cUpsConfigBypassInstalled OBJECT-TYPE SYNTAX INTEGER { unknown (1), yes (2), no (3) } ACCESS read-only STATUS optional DESCRIPTION "Indicates if a bypass is installed in the UPS." ::= { ls43cUpsConfig 1 } -- -- The Liebert Series 4300 UPS Bypass group. -- ls43cUpsBypass OBJECT IDENTIFIER ::= { luSeries4300 13 } ls43cUpsOnBypass OBJECT-TYPE SYNTAX INTEGER { unknown (1), yes (2), no (3) } ACCESS read-only STATUS optional DESCRIPTION "Indicates that the UPS is currently on bypass." ::= { ls43cUpsBypass 1 } ls43cUpsBypassFrequency OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-only STATUS optional DESCRIPTION "The current bypass frequency. (Unit of measure: Hertz)" ::= { ls43cUpsBypass 2 } ls43cUpsBypassNumLines OBJECT-TYPE SYNTAX INTEGER (1..3) ACCESS read-only STATUS optional DESCRIPTION "The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table." ::= { ls43cUpsBypass 3 } ls43cUpsBypassTable OBJECT-TYPE SYNTAX SEQUENCE OF Ls43cUpsBypassEntry ACCESS not-accessible STATUS optional ::= { ls43cUpsBypass 4 } ls43cUpsBypassEntry OBJECT-TYPE SYNTAX Ls43cUpsBypassEntry ACCESS not-accessible STATUS optional INDEX { ls43cUpsBypassLine } ::= { ls43cUpsBypassTable 1 } Ls43cUpsBypassEntry ::= SEQUENCE { ls43cUpsBypassLine INTEGER, ls43cUpsBypassVoltage INTEGER, ls43cUpsBypassCurrent INTEGER } ls43cUpsBypassLine OBJECT-TYPE SYNTAX INTEGER (1..3) ACCESS read-only STATUS optional DESCRIPTION "The bypass Line." ::= { ls43cUpsBypassEntry 1 } ls43cUpsBypassVoltage OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-only STATUS optional DESCRIPTION "The bypass voltage. (Unit of measure: Volt)" ::= { ls43cUpsBypassEntry 2 } ls43cUpsBypassCurrent OBJECT-TYPE SYNTAX INTEGER (0..65536) ACCESS read-only STATUS optional DESCRIPTION "The bypass current. (Unit of measure: Amp)" ::= { ls43cUpsBypassEntry 3 } END